beautypg.com

12 periodic actions, 1 inserting the cables – SMA SSM-U-1615 User Manual

Page 62

background image

12 Periodic Actions

12.1 Inserting the Cables

12.1.1 Leading Cables through Enclosure Opening with

Membrane

Property damage due to dust intrusion and moisture penetration
Excessively large or redundant holes in the membranes of the cable feed-through plate can cause
dust or moisture to penetrate the DC subdistribution.

• Only pierce as many holes in the membrane as you need for the cables.
• The hole in the membrane must be smaller than the diameter of the cable to be led through.

Procedure:

1. Pierce the appropriate membrane.
2. Insert the cable through the membrane.
3. Cut the cable to length.

12.1.2 Leading Cables through Enclosure Opening with Cable

Gland

Seal insert for cable glands for DC main cables:
Cable glands for the DC main cables are each supplied with two seal inserts for different cable
sizes.

Cable diameter

Seal insert

24.0 mm to 38.5 mm

Use mounted seal insert.

17.0 mm to 31.0 mm

Replace seal insert for the seal insert supplied in
the scope of delivery.

Procedure:

1. Release cable gland.
2. Remove the filler plug from the cable gland.
3. When inserting the DC main cables, replace the seal insert with the insert in the scope of

delivery if necessary (see above table).

4. Lead the cable through the swivel nut of the cable gland. Ensure that the thread of the swivel

nut is facing upwards.

5. Lead the cable through the seal insert.
6. Insert the seal insert into the cable gland together with the cable.
7. Cut the cable to length.
8. Tighten the cable gland with the appropriate torque:

12 Periodic Actions

SMA Solar Technology AG

Operating Manual

SSMUXX15-BE-en-10

62

This manual is related to the following products: