2 leds of the network connection, Leds of the network connection – SMA SSM-U-1615 User Manual

Page 50

background image

LED

Status

Cause and corrective measure

COM (yellow)

Off*

At present no data exchange in progress.

On

At present data exchange in progress.

flashing

At present no data exchange in progress.

* If the LED ERR is on, an error has occurred.

9.1.2

LEDs of the Network Connection

LED

Status

Cause and corrective measure

LK/ACT (green)

Off

No network connection established.
The DC subdistribution is not connected to the volt-
age supply.
Corrective measures:

• Connect the DC subdistribution to the voltage

supply.

No network connection established.
The network cable is not properly connected to the
DC subdistribution or other devices in the communica-
tion bus.
Corrective measures:

• Ensure that the network cables are correctly

connected to the DC subdistribution (see
Section 6.4, page 36).

• Ensure that the network cables are correctly

connected to the other devices in the
communication bus.

No network connection established.
One or more network components, network cables or
connectors are defective or damaged.
Corrective measures:

• Replace the defective or damaged network

components, network cables or connectors.

on

Network connection established.

flashing

Network connection established.
Data is being sent or received.

SPEED (yellow)

Off

Network connection established.
The data transfer rate is up to 10 Mbit/s.

on

Network connection established.
The data transfer rate is up to 100 Mbit/s.