Troubleshooting

9.1

LED States

9.1.1

Status LEDs of the SMA String-Monitor

An overview of the LEDs can be found in Section 4.7, page 20.

LED

Status

Cause and corrective measure

UPD (yellow)

Off*

No update in progress at present.

flashing

Update in progress at present.

ERR (red)

On

The electronic assembly is defective.
Corrective measures:

• Contact the Service (see Section 15, page 74).

Off

Normal operation

AL (green)

Off*

The firmware is faulty.
Corrective measures:

• Update the firmware of the SMA String-Monitor

(see inverter manual).

On

The firmware is faulty.
Corrective measures:

• Update the firmware of the SMA String-Monitor

(see inverter manual).

flashing

The firmware is OK.

PWR (green)

Off

Supply voltage is too low or too high.
Corrective measures:

• Make sure that the supply voltage to the DC

subdistribution is OK.

– If you are using the power supply assembly

for the external power supply (available as an
accessory), ensure that the external 230 V

AC

supply voltage is correctly connected (see
manual "Power Supply Assembly for External
Power Supply of SMA String-Monitors").

– Ensure that the supply voltage of the DC

subdistribution from the PV field is correctly
connected.

On

The supply voltage is OK.

9 Troubleshooting