9 troubleshooting, 1 led states, 1 status leds of the sma string-monitor – SMA SSM-U-1615 User Manual
Page 49: Troubleshooting, Led states, Status leds of the sma string-monitor, 9troubleshooting

9
Troubleshooting
9.1
LED States
9.1.1
Status LEDs of the SMA String-Monitor
An overview of the LEDs can be found in Section 4.7, page 20.
LED
Status
Cause and corrective measure
UPD (yellow)
Off*
No update in progress at present.
flashing
Update in progress at present.
ERR (red)
On
The electronic assembly is defective.
Corrective measures:
• Contact the Service (see Section 15, page 74).
Off
Normal operation
AL (green)
Off*
The firmware is faulty.
Corrective measures:
• Update the firmware of the SMA String-Monitor
(see inverter manual).
On
The firmware is faulty.
Corrective measures:
• Update the firmware of the SMA String-Monitor
(see inverter manual).
flashing
The firmware is OK.
PWR (green)
Off
Supply voltage is too low or too high.
Corrective measures:
• Make sure that the supply voltage to the DC
subdistribution is OK.
– If you are using the power supply assembly
for the external power supply (available as an
accessory), ensure that the external 230 V
AC
supply voltage is correctly connected (see
manual "Power Supply Assembly for External
Power Supply of SMA String-Monitors").
– Ensure that the supply voltage of the DC
subdistribution from the PV field is correctly
connected.
On
The supply voltage is OK.
9 Troubleshooting
SMA Solar Technology AG
Operating Manual
49