beautypg.com

2 grounding, 1 information on grounding, 2 grounding the electronic assembly – SMA SSM-U-1615 User Manual

Page 27: 3 grounding the dc surge arrester, Grounding, Information on grounding, Grounding the electronic assembly, Grounding the dc surge arrester

background image

Position

Designation

E

Electronic assembly

F

Strain relief for the cables

6.2

Grounding

6.2.1

Information on Grounding

The parts to be grounded can be connected to a joint grounding electrode.

6.2.2

Grounding the Electronic Assembly

Cable requirement:

☐ Conductor cross-section: 6 mm

2

Procedure:

1. Lead the grounding cable through the corresponding enclosure opening (see Section 6.1,

page 25) into the DC subdistribution (see Section 12.1, page 62).

2. Strip the grounding cable by 15 mm. Make sure that no pieces of cable are dropped into the

DC subdistribution.

3. Connect the grounding cable to the electronic assembly at screw terminal X8 FE (see

Section 4.4, page 17) to ground the electronic assembly.

4. Ensure that the grounding cable is securely fixed.
5. Attach the grounding cable to the strain relief in the DC subdistribution using a cable tie.
6. Ground the grounding cable in the vicinity of the DC subdistribution, e.g. by means of a

grounding electrode.

6.2.3

Grounding the DC Surge Arrester

In order to guarantee the function of the DC surge arrester, it must be connected to the external
grounding.

Cable requirements:

☐ Conductor cross-section: 16 mm

2

to 35 mm

2

☐ Recommended cable type: NYY-O

Procedure:

1. Lead the grounding cable through the corresponding enclosure opening (see Section 6.1,

page 25) into the DC subdistribution (see Section 12.1, page 62).

2. Strip the grounding cable by 15 mm. Make sure that no pieces of cable are dropped into the

DC subdistribution.

3. Route the grounding cable in the cable channel to the connecting terminal plate for functional

grounding of the DC surge arrester (see Section 4.4, page 17). To do this, you can remove
and reattach the cover of the cable channel.

6 Installation

SMA Solar Technology AG

Operating Manual

27

SSMUXX15-BE-en-10

This manual is related to the following products: