Technical Data

SMA America, LLC

98

SB50US-80US-IA-en-37

Installation Manual

Efficiency

Ambient Conditions

Mechanical Data

Specifications subject to change without notice. Values under nominal conditions.

Range of output power factor

0.95 … 1.0

Output power factor, nominal value

0.99

Peak inverter efficiency

96.5 %

CEC weighted efficiency at 240 V AC

96.0 %

CEC weighted efficiency at 277 V AC

96.0 %

Ambient temperature range SB 8000US

− 13 °F … +113 °F

( − 25 °C … +45 °C)

Ambient temperature range SB 8000US-12

− 40 °F … +113 °F

( − 40 °C … +45 °C)

Width x height x depth

18

3

8

in. x 24

1

8

in. x 9

1

16

in.

(468 mm x 613 mm x 242 mm)

Weight

147 lb. (67 kg)

Noise emission

49 dB(A)

Electronics degree of protection

NEMA 3R

86

88

90

92

94

96

98

97

95

300

480

SB 8000-US

0.4

1.0

0.8

0.2

0.6

Output power / Rated power

0.0

Efficency [%]

V

[V]

MPP

V = 300 V DC

V

V

PV

PV

PV

= 345 V DC

= 480 V DC

*

w

eighted

in

accordance

with

CEC-operating

p

oints

weighted Eta* [%]