16. Tighten all cables in the AC and DC terminal blocks in the Sunny Boy:

17. Check whether all connections are correctly wired. Carry out a tensile test to see whether all

cables are tight.

12. Pull the DC cables from the SMA DC disconnect

inside the Sunny Boy.

13. Pull the cable back slightly so as to seal the sealing

grommet.

14. Connect the black cable (PV UNGROUNDED) to

the terminal labeled DC+ in the Sunny Boy.

15. Connect the white cable (PV GROUNDED) to the

terminal labeled DC − in the Sunny Boy.

Gray terminal blocks (Weidmüller)

10 … 6 AWG: 18 in-lb. (2 Nm)

Green terminal blocks (Phoenix)

8 … 6 AWG: 40 in-lb. (4.5 Nm)
10 AWG: 22 in-lb. (2.5 Nm)