beautypg.com

SMA SB 5000-US User Manual

Page 53

background image

SMA America, LLC

Electrical Connection

SB50US-80US-IA-en-37

SB50US-80US-IA-en-37

53

10. Tighten all cables in the AC and DC terminal blocks in the SMA DC disconnect:

11. Check whether all connections are correctly wired. Carry out a tensile test to see whether all

cables are tight.

6. Pull the DC cables from the SMA DC disconnect

inside the Sunny Boy.

7. Pull the cable back slightly so as to seal the sealing

grommet.

8. Connect the white cable (PV GROUNDED) to the

terminal labeled DC+ in the Sunny Boy.

9. Connect the black cable (PV UNGROUNDED) to

the terminal labeled DC − in the Sunny Boy.

Gray terminal blocks (Weidmüller)

10 … 6 AWG: 18 in-lb. (2 Nm)

Green terminal blocks (Phoenix)

8 … 6 AWG: 40 in-lb. (4.5 Nm)
10 AWG: 22 in-lb. (2.5 Nm)

2 3 5 7

A B + -

2

4

0

V

2

7

7

V

2

0

8

V

2 3 5 7

A B + -

2

4

0

V

2

7

7

V

2

0

8

V

This manual is related to the following products: