Troubleshooting

SMA America, LLC

80

SB50US-80US-IA-en-37

Installation Manual

Interference

VacL1-Ocu, VacL2-
Ocu, VacL1-Srr, VacL2-
Srr

Voltage is too high or too low on the indicated
branch.

Interference

VpvMax
!PV Overvoltage!
!Disconnect DC!

The DC input voltage is exceeding the maximum
tolerable value.
Disconnect the DC line immediately.

Interference

Watchdog

Watchdog for operation control triggered.

Interference

XFMR

The transformer is connected to the wrong grid.
Check the connection of the transformer.
For grounded Delta grids: Monitor whether the
grid grounding conductor is connected to
terminal L2.
In the event of unbalanced load in 200 V and
240 V grids, swapping L1 and L2 may rectify the
fault.

Interference

XFMR_TEMP_F

High transformer temperature. The Sunny Boy
stops and the fans run at maximum speed.

Warning

XFMR_TEMP_W

After the reduction of the high transformer
temperatures, the Sunny Boy restarts. Monitor the
function of the fans.

Error type

Error code

Description