Technical Data

SMA America, LLC

100

SB50US-80US-IA-en-37

Installation Manual

11.6 Trip Limits/Trip Times

Frequency

Voltage

* The intervals result from the measuring accuracies listed below.

Accuracy

Trip limits: ±2 % of nominal grid voltage
Trip time: ±0.1 % of nominal trip time
Trip frequency: ±0.1 % of nominal frequency

Nominal

Frequency

Trip Limit

Trip Frequencies

Trip Times

60 Hz

> 60.5 Hz

60.45 Hz … 60.55 Hz

max. 0.1602 s

< 57.0 Hz … 59.8 Hz

(standard 59.3 Hz)

56.95 Hz … 59.85 Hz

(standard 59.25 Hz …

59.35 Hz)

adjustable, 0.16 s … 300 s

(standard max. 0.1602 s)

< 57.0 Hz

56.95 Hz … 57.05 Hz

max. 0.1602 s

Nominal

Voltage

Trip Limit

Trip Voltages

Conductor-

Neutral

Conductor*

Trip Voltages

Conductor-

Conductor*

Trip Times

208 V

50 %
88 %

110 %
120 %

57.6 V … 62.4 V

103.2 V … 108.0 V
129.6 V … 134.4 V
141.6 V … 146.4 V

99.8 V … 108.2 V

178.9 … 187.2 V

224.6 V … 233.0 V
245.4 V … 253.8 V

max. 0.1602 s

max. 2.002 s
max. 1.001 s

max. 0.1602 s

240 V

50 %
88 %

110 %
120 %

57.6 V … 62.4 V

103.2 V … 108.0 V
129.6 V … 134.4 V
141.6 V … 146.4 V

115.2 V … 124.8 V
206.4 V … 216.0 V
259.2 V … 268.8 V
283.2 V … 292.8 V

max. 0.1602 s

max. 2.002 s
max. 1.001 s

max. 0.1602 s

277 V

50 %
88 %

110 %
120 %

133.0 V … 144.0 V
238.2 V … 249.3 V
299.2 V … 310.2 V
326.9 V … 337.9 V

Not applicable

max. 0.1602 s

max. 2.002 s
max. 1.001 s

max. 0.1602 s