11.2 Sunny Boy 6000-US (SB 6000US and SB 6000US-12)

PV Array Connection

Grid Connection

General Data

Maximum MPP voltage

250 V … 480 V

Nominal operating voltage

310 V

Range of input operating voltage

250 V … 600 V

Maximum generator input power

7 500 W

Maximum DC power

6 400 W

PV start voltage

300 V

Maximum DC input current

25 A

Maximum input short-circuit current

36 A

Maximum utility backfeed current to PV array

50 A AC

DC voltage ripple

< 10 %

AC operating voltage range at 208 V nominal value

183 V … 229 V

AC operating voltage range at 240 V nominal value

211 V … 264 V

AC operating voltage range at 277 V nominal value

244 V … 305 V

AC operating frequency range

59.3 Hz … 60.5 Hz

AC frequency, nominal value

60 Hz

Maximum continuous AC output power

6 000 W

Current THD

< 4 %

Maximum continuous AC output current at 208 V

29 A

Maximum continuous AC output current at 240 V

25 A

Maximum continuous AC output current at 277 V

21.6 A

Maximum output failure current

57.6 A

Maximum output overcurrent protection

50 A

Synchronization of inrush current

9.23 A

Trip limit accuracy

±2 %

Trip time accuracy

±0.1 %

Power consumption at night

0.1 W

Inverter technology

True sine, low-frequency transformer

Cooling concept

OptiCool