beautypg.com

1 wiring with dc disconnect, Wiring with dc disconnect, Procedure and order – SMA SB 5000-US User Manual

Page 39

background image

SMA America, LLC

Electrical Connection

SB50US-80US-IA-en-37

SB50US-80US-IA-en-37

39

6.2.1 Wiring with DC disconnect

Procedure and Order

1. Switch off all energy sources. Open all AC and DC disconnect switches and breakers.
2. Wiring from AC breaker to DC disconnect.
3. AC wiring from DC disconnect to Sunny Boy.
4. Wiring from PV array to DC disconnect.
5. DC wiring from DC disconnect to Sunny Boy.
6. Switch DC disconnect to position "1".
7. Switch on AC breaker.

Removing Sunny Boy from Wiring

• Disconnect all AC disconnect switches.
• Switch DC disconnect to position "0".
• Always disconnect the AC side before the DC side.
• When the Sunny Boy is switched off, remove the wiring in reverse order.