background image

SMA America, LLC

Maintenance

SB50US-80US-IA-en-37

SB50US-80US-IA-en-37

89

4. Check the DC varistors (A) for discoloration and visible damage.

• If one of the DC varistors is discolored or damaged, replace all DC varistors:

5. Disconnect the DC varistors:

– Disconnect the string connectors of all ungrounded DC cables from the PV array.
– Remove the four fuse extractors with the string fuses from the fuse holders (B) of the DC

disconnect.

– Remove the four string fuses from the fuse extractors.
– Insert the four fuse extractors without the string fuses into the fuse holders (B) of the DC

disconnect.

6. Ensure that no voltage is present at the DC varistors.

• If no voltage is present, replace all DC varistors:

– Insert the insertion tool into the rectangular

opening of the terminal.

– Remove the DC varistor.

DANGER

Danger to life due to short circuits in the DC varistors
Death or serious injury due to electric shock

• Check whether current is flowing the DC cables.

Tip: Use a current clamp to measure the current.

Only use spare parts from SMA

• Always replace the entire set of DC varistors.
• Order number in Section 12 ”Spare Parts and Accessories” (page 101).