Displays and Messages

SMA America, LLC

76

SB50US-80US-IA-en-37

Installation Manual

Operating Mode

MPP-Operation,

Turbine, V-const,

Stop

MPP

Electrically

qualified

person

Operating modes of the Sunny Boy:
MPP-Operation: Sets the Sunny Boy

in Maximum Power Point Tracking

Mode
V-const: Constant Voltage Mode

(target value defined in "Vconst-

Setval")
Turbine: Operating mode for wind

turbine systems
Stop: Disconnection from grid, no

operation

V-Const Setval

G

SB 5000-US -

SB 7000-US:

250 ... 600
SB 8000-US:

300 ... 600

600

Electrically

qualified

person

PV target voltage for constant

voltage operation. These

parameters only are important in the

event that the parameter "Operating

Mode" is set to "V-const".

Vac-Min*

%

0 ... 50

12

Electrically

qualified

person

Values are used to calculate the

lower limit of permissible AC

voltage.
Standard value is optimal for plants

< 30 kW. Standard value 12 results

in a trip value of 88 %, as the list of

trip limits shows.

Vac-Max*

%

0 ... 20

10

Electrically

qualified

person

Values are used to calculate the

upper limit of permissible AC

voltage.
Standard value is optimal for plants

< 30 kW. Standard value 10 results

in a trip value of 110 %, as the list of

trip limits shows.

Vac-Min-Fast*

%

0 ... 50

50

Electrically

qualified

person

Values are used to calculate the

lower limit of allowable AC voltage

for fast disconnection. Standard

value is optimal for plants < 30 kW.

Standard value 50 results in a trip

value of 50 %, as the list of trip limits

shows.

Vac-Max-Fast*

%

0 ... 20

20

Electrically

qualified

person

Values are used to calculate the

upper limit of allowable AC voltage

for fast disconnection. Standard

value is optimal for plants < 30 kW.

Standard value 20 results in a trip

value of 120 %, as the list of trip

limits shows.

Vac-Min-Recnet

%

0 ... 50

11.7

Electrically

qualified

person

Values are used to calculate the

lower and upper limits to reconnect

to the grid after a grid failure.

Vac-Max-Recnet

%

0 ... 20

5.83

Electrically

qualified

person

Name

Unit

Range

Standard

Password

Level

Description