Electrical Connection

SMA America, LLC

36

SB50US-80US-IA-en-37

Installation Manual

6 Electrical Connection

DANGER

High voltages on the AC and DC cables
Risk of death or serious injury due to electric shock.

• Only connect the inverters as described in this manual.
• Only electrically qualified persons may work on the inverter.

NOTICE

Ingress of moisture when mounting and installing the Sunny Boy
Potential damage to the Sunny Boy.

• For conduit hubs, use UL listed raintight, wet location hubs for entry into the enclosure.
• Do not open the Sunny Boy in the event of rain or a high level of humidity (> 95 %).

Damage to the seal of the enclosure lid during frost
When opening the Sunny Boy during frost, the seal of the enclosure lid can be damaged.
There may be an ingress of moisture damaging the Sunny Boy.

• Do not open the Sunny Boy when the outdoor temperature is below 23 °F ( − 5 °C).

Electrostatic discharges through touching component parts
Potential damage to the Sunny Boy.

• Ground yourself before touching any electronic component.

Ground faults, unreliable and highly resistive connections due to Wire Nuts

®

Potential damage to or failure of the Sunny Boy.

• Do not use Wire Nuts

®

.

Electrical Installations
All electrical installations must be carried out according to the applicable electrical
standards on site and the National Electrical Code ANSI/NFPA 70. Installations in
Canada must be carried out according to the applicable Canadian standards.
Before connecting the Sunny Boy to the power distribution grid, contact your local electric
utility company. This connection must be made only by qualified personnel.