Page 59

background image

Additional data volume when using the Sunny
Portal live interface

600 kB/hour

Topology

transformerless

Cooling concept

SMA OptiCool

Fan connection

Designed for safe disconnection in accordance

with DIN EN 62109

Degree of protection for electronics in accor-
dance with IEC 60529

IP65

Protection class in accordance with IEC 62103

I

Grid configurations

TN-C, TN-S, TN-C-S, TT (when V

N_PE

< 20 V)

Approvals and national standards, as per
06/2014*

AS 4777, CE, CEI 0-21, C10/11:2012,

DIN EN 62109-1, EN 50438, G59/3,

G83/2, IEC 61727/MEA IEC 61727/PEA,

IEC 62109-2, NEN EN 50438, NRS 097-2-1,

PPC, PPDS, RD 661/2007, RD 1699:2011,

SI 4777, UTE C15-712-1, VDE0126-1-1, VDE-

AR-N 4105, VFR 2013, VFR 2014

* AS 4777, SI 4777: For STP 12000TL-20 available as of October 2014

CE, EN 50438, G59/3, G83/2, IEC 62109-2, NEN EN 50438, NRS 097-2-1, PPC, PPDS,
RD 661/2007, RD 1699:2011, UTE C15-712-1, VDE AR-N 4105, VFR 2013, VFR 2014:
For STP
12000TL-20 available as of September 2014
CEI 0-21: only permitted with external decoupling protection. For STP 12000TL-20 available as of
September 2014
C10/11:2012: only possible if the three-phase line-to-line voltage is 400 V.
IEC 61727/MEA and IEC 61727/PEA:only applicable for STP 9000TL-20.
EN 50438: does not apply to all national appendices of EN 50438.
IEC 62109-2: This standard requires that either the multifunction relay in the inverter is used as fault
indicator or that the inverter is connected to Sunny Portal and that the fault alert is activated in
Sunny Portal.
NRS 97-2-1: This standard requires a separate label be attached to the AC distribution board to
indicate the AC-side disconnection of the inverter in case of a grid failure (for further details, see
NRS 97-2-1, Sect. 4.2.7.1 and 4.2.7.2).

11.3 Protective Devices

DC reverse polarity protection

Short-circuit diode

Input-side disconnection point

Electronic Solar Switch, SUNCLIX DC connector

DC overvoltage protection

Thermally monitored varistors

AC short-circuit current capability

Current control

Grid monitoring

SMA Grid Guard 4

Maximum permissible fuse protection

32 A

11 Technical Data

SMA Solar Technology AG

Operating Manual

59

STP5-10TL-20-BE-en-13