6.2.2 Interior View

Figure 7: Connection areas in the interior of the inverter

Position

Designation

A

Connecting terminal plate for the AC cable

B

Multifunction relay with protective cover

C

Slot for 485 Data Module Type B or SMA Power Control Module

D

Varistors

6.3 AC Connection

6.3.1 Requirements for the AC Connection

Cable requirements:

☐ External diameter of the cable must correspond to the clamping range of the cable gland:

12 mm to 21 mm

☐ Recommended conductor cross-section for stiff or flexible cables, with or without bootlace

ferrule: 1.5 mm² to 6 mm²

6 Electrical Connection