6.5.2 Connection to the Multifunction Relay

Figure 11: Connecting terminal plate for the connection to the multifunction relay

Requirement:

☐ The technical requirements of the multifunction relay must be met (see Section 11 "Technical

Data", page 53).

Cable requirements:

☐ The cable must be double-insulated.
☐ External diameter: 5 mm to 12 mm
☐ Conductor cross-section: 0.08 mm² to 2.5 mm²
☐ The cable type and cable-laying method must be appropriate for the application and location.

Destruction of the multifunction relay as a result of excessive contact load

Observe the maximum switching voltage and maximum switching current (see Section 11.7

"Multifunction relay", page 61).

• When connecting the multifunction relay to the utility grid, fuse the multifunction relay with a

separate circuit breaker.

Operating the multifunction relay and 485 Data Module Type B or
SMA Power Control Module in parallel
If you want to operate the multifunction relay and the 485 Data Module Type B or the
SMA Power Control Module in parallel, no more than 30 V DC or 25 V AC must be
connected to the multifunction relay.

6 Electrical Connection

SMA Solar Technology AG

Operating Manual

35