Westermo IDW-90 AT User Manual
Page 70

70
6620-3200
Examples:
Set input min pulse width to 500ms max pulse width to 1s, triggered
on high level and output to follow DCD
*wiop=50,100,1,1,3
OK
Change input type to be pulse triggered
*wiop=,,2,,
OK
*wiop?
*wiop : TMIN=50, TMAX= 100, TYPE=2, TRIG=1, NORM=3
OK
Result Codes: OK
ERROR Otherwise:
*wiot – General IO test
This command executes the specified entry as if it was triggered by the normal trigger
condition.
Syntax:
*wiot =
*wiot =?
IO entry index number (0 – 10) 1 – 10 selects
the entry at the corresponding index in the table.
Selecting entry_num =0 selects the local output,
the state of the output is selected with parameter
IO_state
[,
entry_num is set to 0.
Examples:
*wiot =2
Trigger and execute entry 2 in the table
OK
*wiot =?
*wiot: (0-10)[,(1-1)]
OK
Result Codes: OK
ERROR
Otherwise
- TR-36B (88 pages)
- TD-36 (44 pages)
- TR-36 (36 pages)
- TR-36B (20 pages)
- GD-01 (206 pages)
- GD-01 (20 pages)
- MRI-128-F4G (175 pages)
- MRI-128-F4G (169 pages)
- GDW-11 485 (380 pages)
- GDW-11 (40 pages)
- Lynx Series (28 pages)
- ODW-720-F1 (20 pages)
- ODW-720-F1 (24 pages)
- ODW-720-F2 (36 pages)
- ODW-730-F2 (36 pages)
- ODW-730-F1 (24 pages)
- DDW-120 (24 pages)
- DDW-226-EX (24 pages)
- DDW-226-EX (24 pages)
- DR-270 (28 pages)
- DR Series (460 pages)
- ED-2x0 (20 pages)
- MRD-3x0 (199 pages)
- FD-80 (24 pages)
- FDV-206-1D-1S (24 pages)
- GD-01 US (24 pages)
- LD-01 (8 pages)
- IDW-90 (44 pages)
- Lynx-x10-F2G (16 pages)
- Lynx-x08-F2G-S2 (20 pages)
- MDI-110-F3x (16 pages)
- MR-2x0 (28 pages)
- ODW-642 (28 pages)
- PII PoE Injector (12 pages)
- Viper Series (977 pages)
- SDI-5xx (12 pages)
- RFI-xx (32 pages)
- SDI-8xx (16 pages)
- RFIR-xxx (24 pages)
- TD-29 (16 pages)
- SDW-5xx (24 pages)
- TD-23 (24 pages)
- TD-29P (16 pages)
- Viper 408 (20 pages)