Edit Input Types
Edit Input Types allows the type of thermocouple to be changed for any channel. The
drop-down bar contains a list of thermocouple types. Select the appropriate
thermocouple types. The Range Start and Range End correspond to the channels of the
SDS that will be changed. To change only one channel, set the Range Start and Range
End both to that number. To change all channels, the Range Start will be 1 and the
Range End will be 20. Any interval in between can also be used. Press Set Range Input
Types to save.
Figure 35 - Edit Input Types
Edit Offsets
The Edit Offsets option will change the offset for each thermocouple. Press the blue
number button next to Select Input and enter the appropriate channel number. Press
OK. Then enter the Offset Value and press OK.
NOTE: These offsets should be used to address the calibration report parameters to
correct for a known deviation by individual channel at a specific temperature OR to
compensate for an individual thermocouple wire for each channel. All offsets that are
used can be displayed on the final report using the reporting tags.