Ice thickness sensor

1. Push and release the Off switch.
2. Remove front and top panels.
3. Push and release the Harvest switch
4. Remove the evaporator cover.
5. Disconnect electrical power.

6. Open the control box.
7. Remove left most curtain.
8. Locate sensor, squeeze mounting legs together to

release it from the mounting bracket.

9. Remove sensor, follow wire back to control box.
10. Disconnect from controller connection J10.
11. Remove sensor from machine.
12. Reverse to reassemble.
13. Set initial probe-to-evaporator-surface gap using a 7/32” drill bit as a gauge. Bridge thickness adjustments

may be needed. Operate machine and to confirm and adjust ice bridge.

Electrical Shock Hazard
Disconnect electrical

power before beginning