Diagnostics – Remote Air Cooled
No ice
Problem
Likely Cause
Probable Solution
No power to unit
Power disconnected Check breaker or fuse.
Reset or replace, restart and check
No power to controller
Transformer open
Replace transformer
Shut down on maximum
water fill time
Water shut off
Restore water supply
Shut down on maximum
freeze time
Water leak
Check purge valve, curtain, sump, pump
hose
Dirty condenser
Clean condenser
Restricted location, intake air too hot
Have condenser moved
Ice thickness sensor dirty or disconnected
Check ice thickness sensor probe
Water distributor dirty
Remove and clean water distributor
Inlet water valve leaks through during freeze
Check inlet water valve
Connected to hot water
Check for bleed thru from / missing check
valve in building water supply
Incomplete harvest
Check harvest system
High pressure cut out opened
Check fan motor pressure control, check
fan motor, check controller using test
mode
Fan motor not turning
Check fan motor, check fan blade
Water pump not pumping
Check pump motor, check controller
using test mode
Pump hose disconnected
Check hose
Compressor not operating
Check compressor contactor, check
controller using test mode
Check compressor start components,
check PTCR resistance and temperature
Check compressor voltage
Check compressor windings
Low refrigerant charge
Add some refrigerant and restart unit. If
cycle time improves, look for leak.
Hot gas valve leaks through during freeze
Check hot gas valve for hot
outlet during freeze
Thermostatic expansion valve bulb loose
Check bulb
Thermostatic expansion valve producing very
low or very high superheat
Check evaporator superheat, change
TXV if incorrect
Liquid line valve does not open
Check coil of valve, check controller
using test mode
Compressor inefficient
Check compressor amp draw, if low and
all else is correct, change compressor
Debris in refrigeration system
Recover charge. Open quick connects,
check for loose or missing foil. Open
liquid line and hot gas valves. Check for
debris. Replace drier, evacuate and
weigh in nameplate charge.