Programming, Vav/zone controller damper force modes – Orion System SA Controller User Manual
Page 54
Zone
Zone
Programming
SA Controller Operator Interface
54
Damper Force Modes
Damper Force Modes are available for testing or balancing the system.
These Force Modes can be accessed and programmed from either the
System Manager or the Modular Service Tool.
System Manager Instructions
To access the Damper Force Modes from the System Manager, press
the
< Setpoints>
button. You will then see the Unit ID Screen. Enter
the unit ID of the controller you wish to access and press
. The
following screen will appear:
1) Change Setpoint
2) Configure Unit
3) Dampers Force
ESC) Exit Menu
Press
<3>
on the keypad and then
. You will then see the Unit
ID Screen. Enter the unit ID of the controller you wish to access and
press
. At this time, the Password Screen will be displayed.
Enter your level 2 password, press
, and the following screen
will be displayed:
1) Outputs Force
2) Dampers Force
Press
<2>
to access the Damper Force Modes Screen. Please note: 1)
Outputs Force is not available with the System Manager.
Modular Service Tool Instructions
When using the Modular Service Tool, simply press the
< Balance-
Test>
button. You will then see the Unit ID Screen. Enter the unit ID
of the controller you wish to access and press
. The following
screen will be displayed:
1) Outputs Force
2) Dampers Force
Press
<2>
to access the Dampers Force Modes Screen. Please note: 1)
Outputs Force is available with the Modular Service Tool, but is not
used with the VAV/Zone controller.
Dampers Force Mode Screen
If the unit ID you entered is for a SA Controller that has VAV/Zone
controllers connected to its communication loop, the Damper Force
Mode will act as a “Global” Damper Force Mode. That is, all VAV/Zone
controllers on that SA Controller’s communication loop will be forced
to the same Damper Force Mode setting. If the unit ID you entered is
for a VAV/Zone controller, the Damper Force Mode setting will only
apply to that VAV/Zone controller.
Damper Force ID 102
Enter Force Mode: 0
0=Auto 1=Open 2=Clsd
3=Max 4=Min 5=Fixed
Set the appropriate Damper Force Mode by entering numbers 0 through
5. The Force Modes for each of these settings is outlined below.
0 = Auto
This is the default setpoint. With this setting,
the damper will operate normally and modulate
according to the controller setpoints.
1= Open
This setting will force the damper to its fully-
open
position.
2= Clsd
This setting will force the damper to its fully-
closed
position.
3= Max
This setting will force the damper to the damper’s
maximum
airfl ow position set under VAV/Zone
Controller
Setpoint
Screen
#5 (see page 48).
4= Min
This setting will force the damper to the current
mode’s minimum position setpoint. These modes
are Vent Mode, Heat Mode, and Cool Mode. They
may each have a different minimum depending on
how
you
confi gured the setpoints. See VAV/Zone
Controller
Setpoint
Screen
#5
on page 48.
5= Fixed
This setting will force the damper to a fi xed
position
based
on
the
fi xed position setpoint.
See
VAV/Zone Controller Setpoint Screen #8 on
page 49 for available setpoint information.
Caution: The Damper Force Modes should only be used by quali-
fi ed service personnel. Serious damage to the ductwork
could result if the dampers are all forced closed and the
HVAC unit fan is operating.
VAV/Zone Controller Damper Force Modes