Programming, Vav/zone controller status screens, Status – Orion System SA Controller User Manual

Page 52

background image

Zone

Zone

Programming

SA Controller Operator Interface

52

VAV/Zone Controller

Status

Status Screen #1 - Mode of Operation

XX Box v4.01 IDXXXX

Occupied Mode

Vent Mode

Belongs to Group # 1

Line 2 Unoccupied Mode

Occupied Mode

Override Mode

Override Pending*

Damper Calibration

Group Override

Line 3 OFF Mode

Vent Mode

Cooling Mode

Heating Mode

Sensor Fail Mode**

Line 4 Belongs to Group # xx

No Group Affi liation

* Not displayed when using a Digital Room Sensor.

** Displays for either a temperature sensor failure or an airfl ow
sensor failure.

Status Screen #2 - Zone Temperature and

Cooling/ Heating Setpoints

XX Box v4.01 IDXXXX

Zone Temp..: XX.XºF

Cooling Spt: XX.XºF
Heating Spt: XX.XºF

Line 2 Current Zone Temperature

Line 3 Currently active Cooling Setpoint based on the current

Occupied / Unoccupied mode of operation.

Line 4 Currently active Heating Setpoint based on the current

Occupied / Unoccupied mode of operation.

Status Screen #3 - Slide Offset & H/C Demand

XX Box v4.01 IDXXXX

Slide Offset: XXºF

H/C Demand.: XX.XºF

Line 2 If the optional Setpoint Slide Adjust is installed on the

Flush Mount Wall Sensor, this line will display the

current

amount

the

Slide Offset is affecting the

Heating and Cooling Setpoints.

Line 3 Current

Heating or Cooling Demand in the Zone

based on the current Heating and Cooling Setpoints

when compared to the current Zone Temperature.

Line 4 Blank

Status Screen #4 - Supply Air Temperature &

Box Air Temperature

XX Box v4.01 IDXXXX

Supply Air: XX.XºF

Box Air..: XX.XºF

Line 2 Current Supply Air Temperature received via

broadcast from the DX Air Handler or from the Box

Controller’s own installed Box Air Temperature Sensor

connected to the AUX input of the VAV/Zone

controller

board.

Line 3 Current Box Air Temperature

If you have confi gured the SA Controller to

broadcast the Supply Air Temperature to the VAV/

Zone controller and don’t have a Box Air Temperature

Sensor attached to the AUX input on the VAV/Zone

controller board, this line will display the Supply Air

Temperature the same as line 2.

If you have a Box Air Temperature Sensor attached to

the AUX input on the VAV/Zone controller board, this

line will display the Box Air Temperature at the

location where the Box Air Temperature Sensor is

installed.

Line 4 Blank

VAV/Zone Controller Status Screens