beautypg.com

System confi guration, Mua and heat pump confi gurations, Sa controller operator interface 16 mua unit – Orion System SA Controller User Manual

Page 16: Heat pump

background image

Zone

Zone

System Confi guration

SA Controller Operator Interface

16

MUA Unit

If you need to set up your HVAC unit for MUA operation, use the fol-
lowing values:

Confi guration Section

Screen #1—Duct Static Pressure Control = “NO”

Screen #3—HVAC Mode Enable = “Entering Air”

Screen #4—HVAC Reset Source = “No Reset”
Can be confi gured for Reset; see the Supply Air Setpoint Reset
section that follows before confi guring.

Screen #6—Dehumidifi cation Control = “YES”
Only if the unit is equipped for Dehumidifi cation.

Screen #7—Dehumidifi cation Priority = “YES”

Screen #8—Dehumidifi cation Unoccupied = “NO”

Screen #9—Entering Air Humidity Sensor = “YES”
Only if equipped with an Entering Air Humidity Sensor for
Dehumidifi cation.

Screen #14—Proof of Flow Input = “YES”
Only if equipped with a Proof of Flow Switch.

Screen #28— Emergency Shutdown Input = “YES”
Only if a Smoke Detector, Firestat, or other Shutdown device is
connected to the SA Controller.

Screens #41 through #60 = Refer to the AAON

®

wiring diagram

inside the unit before confi guring onboard and expansion board
relays.

Heat Pump

Heat Pumps can be confi gured as VAV, CAV, or MUA. Confi guration
Screens #26 and #27 are used to confi gure the Heat Pump. A Relay Out-
put must be confi gured for a Reversing Valve on Screens #41 through
#60 whether the Reversing Valve is to be activated during Heating or
Cooling operation. When using AAON

®

equipment, if the equipment

is an AAON

®

packaged unit, the Reversing Valve activates during

Heating operation.

Confi guration Section

Screen #26—Heat Pump Control = “YES”

Screen #27—Reversing Valve Active During Heat/Cool =
“0=Heat” if the Reversing Valve should energize for Heating
operation; “1=Cool” if the Reversing Valve should energize for
Cooling operation.

Screens #41 through #60 = Refer to the AAON

®

wiring diagram

inside the unit before confi guring on-board and expansion board
relays.

MUA and Heat Pump Confi gurations