beautypg.com

Programming, Sa controller confi guration screens – Orion System SA Controller User Manual

Page 24

background image

Zone

Zone

Programming

SA Controller Operator Interface

24

SA Controller Confi guration Screens

Confi guration Screens #41-60 - Relay

Confi guration Screens

SA Unit Cnfg ID 102

Relay Configurations

Rly xx: Not Used

Press “0” To Change

Relay #1 is not confi gurable as it is reserved for the Supply Air Fan.
Relays #2-#21 are confi gurable for the following options:

Not

Used

Pre-Heater

Heat Stage

Alarm

Cool Stage

Override

Warmup Mode

Occupied

Rev Valve

WS Economizer

HGR

Relays #2 through #21 can be individually confi gured. By using the
4 relay outputs available on the SA Controller, the 4 relays on the
SA Expansion Module, and the 12 relays on the 12 Relay Expansion
Module, you have the ability to confi gure up to a combined total of 20
Heating Stages, Cooling Stages, and the rest of the options listed above.
Only the Heating and Cooling relays can be confi gured with multiple
outputs. If any other option is selected more than once, it will simply
activate redundant relays, but no multiple staging will occur. Default
is “Not Used.”