Programming, Relay overrides, Sa controller operator interface – Orion System SA Controller User Manual
Page 39
SA Controller Operator Interface
Programming
39
The next screen displays the Relay Overrides for Relay 2. After press-
ing
, the next relay will be displayed. All 20 Relay Override
Screens (including the AHU fan relay) are available by pressing
after each setting is made.
Relay Overrides
Relay 2 Override: 0
[0=Auto 1=ON 2=OFF]
After the screen for relay 21 is displayed, the fi rst Analog Output Over-
ride Screen will be displayed.
Analog Output 1 Screen
Economizer Overrides
Analog Output #1
Override Volts: -1.0
[-1.0=Auto]
The default setting for normal operation is -1.0 volts. Voltages between
0 to 10.0 can be set for any of the Analog Output Overrides. Press
after making a setting change and the next Analog Output
Override Screen will be displayed.
Analog Output 2 Screen
AHU Fan VFD Override
Analog Output #2
Override Volts: -1.0
[-1.0=Auto]
Analog Output 3 Screen
Mod Heating Override
Analog Output #3
Override Volts: -1.0
[-1.0=Auto]
Analog Output 4 Screen
Mod Cool 1 Override
Analog Output #4
Override Volts: -1.0
[-1.0=Auto]
Analog Output 5 Screen
Mod Cool 2 Override
Analog Output #5
Override Volts: -1.0
[-1.0=Auto]
Analog Output 6 Screen
WSE Bypass A Override
Analog Output #6
Override Volts: -1.0
[-1.0=Auto]
Analog Output 7 Screen
WSE Bypass B Override
Analog Output #7
Override Volts: -1.0
[-1.0=Auto]
Relay Overrides