Programming, Sa controller setpoint screens, Sa controller operator interface 26 – Orion System SA Controller User Manual

Page 26: Zone

background image

Zone

Zone

Programming

SA Controller Operator Interface

26

SA Controller Setpoint Screens

Setpoint Screen #1 - HVAC Mode Setpoints

SA Unit Spts ID 102
HVAC Mode Setpoints

Cooling......: 75ºF
Heating......: 70ºF

These Setpoints are used to determine the Heating, Cooling, or Vent
Modes of operation in reference to the HVAC Mode Enable Sensor.
If the Supply Air Sensor is confi gured to be the HVAC Mode Enable,
these Setpoints are used in conjunction with the Unoccupied Setbacks
if equipped with a Space Temperature Sensor.

Description

Minimum

Default

Maximum

HVAC Mode Setpoints Cooling

0ºF

75ºF

99ºF

HVAC Mode Setpoints Heating

0ºF

70ºF

99ºF

Setpoint Screen #2 - HVAC Mode Select

Deadband

SA Unit Spts ID 102

HVAC Mode Select

Deadband....: 1.0ºF

This Setpoint is added to and subtracted from the HVAC Mode Setpoints.
It provides you with fl exibility on when the Heating and Cooling Modes
should be active above or below the HVAC Mode Setpoints.

Description

Minimum

Default

Maximum

HVAC Mode Select Deadband

0ºF

1ºF

10ºF

Setpoint Screen #3 - Unoccupied Setbacks

SA Unit Spts ID 102
Unoccupied Setbacks

Cooling.........: 30ºF
Heating.........: 30ºF

During the Unoccupied Mode of Operation, these Setpoints spread the
HVAC Mode Setpoints out by a user-adjustable amount. Use only posi-
tive numbers for these Setpoints. If you do not want Cooling or Heating
to operate during the Unoccupied Mode, use the default setting of 30°F
for these setpoints.

Description

Minimum

Default

Maximum

Unoccupied Setbacks Cooling

0ºF

30ºF

30ºF

Unoccupied Setbacks Heating

0ºF

30ºF

30ºF

Setpoint Screen #4 - SAT Cooling Setpoints

SA Unit Spts ID 102

SAT Cooling Spts

Cooling..: 55ºF
Rst Limit: 55ºF

If no Reset Source has been confi gured in Confi guration Screen #4, then
this setpoint will be the Supply Air Temperature Cooling Setpoint. Line
4 will be blank. If a Reset Source has been confi gured in Confi guration
Screen #4, then Line 4 will read Rst Limit. Reset is always upward from
the SAT setpoint to the Reset Limit setpoint. So, the SAT will be the
lowest temperature the Supply Air Setpoint can be reset to and Reset
Limit will be the highest temperature the Supply Air Setpoint can be
reset to. The Cooling Supply Air Temperature Setpoint will automati-
cally be reset warmer or colder within this range as the Reset Source
(next screen) moves within its range.

Description

Minimum

Default

Maximum

SAT Cooling Setpoint

30ºF

55ºF

80ºF

Cooling Reset Limit

40ºF

55ºF

200ºF

Setpoint Screen #5 - Cool Reset Source

SA Unit Spts ID 102

Cool Rst Source Spts

EntHi: 75 SAT: 55º
EntLo: 75 RST: 55º

If no Reset Source has been confi gured in Confi guration Screen #4,
then this screen will read Cool Rst Not Confi g and will not be used. If
a Reset Source has been confi gured in Confi guration Screen #4, then
the names of the values on the left side of this screen will correspond to
the Reset Source that was confi gured. This screen will then allow you
to input the upper and lower limits for the range of values of the Reset
Source on the left side of the screen and will show the corresponding
Cooling Supply Air SAT and Rst Limit values that were entered on the
previous screen. Single Zone VAV Reset of the Supply Fan VFD is ad-
dressed in the last paragraph.

Please note that the SAT and Rst Limit values on the right side of this
screen cannot be changed on this screen; they are simply displayed from
what was entered on the Setpoint Screen #4. For each line, the value on
the left corresponds to the value on the right. So, if the Space Temperature
Sensor has been confi gured as the Reset Source, then when the Space
Temperature is at or above the SpcHi Temperature Setpoint, the Supply
Air Cooling Setpoint will be reset to its lowest value, the SAT Setpoint.
If the Space Temperature is at or below the SpcLo Setpoint, the Supply
Air Cooling Setpoint will be reset to its highest value, the Cooling Rst
Limit. Then, as the Space Temperature moves from its low value to its
high value, the Supply Air Cooling Setpoint will be proportionally reset
from its high value to its low value.