Programming, Vav/zone controller status screens, Sa controller operator interface – Orion System SA Controller User Manual
Page 53
SA Controller Operator Interface
Programming
53
Status Screen #5 - Zone Damper Position,
Airfl ow, and Desired CFM
XX Box v4.01 IDXXXX
Damper FRC: XXX %
Airflow : XXXX CFM
Desired : XXXX CFM
Line 2 Current Zone Damper Position
If you entered a FORCE command, the letters FRC
will appear. If this is normal damper operation, the
FRC will not be displayed.
Line 3 If this is a Pressure Independent box, the current
Airfl ow will be displayed. If not, this line will display
the desired damper position.
Line 4 If this is a Pressure Independent box, this line will
display the Desired CFM the box would like to
provide to the zone. If not, this line will display
[Controls to +/- 3%] to indicate how accurately the
damper will maintain the desired position.
Status Screen #6 - Fan Status & Reheat
Stages
XX Box v1.04 IDXXXX
Fan Status : OFF
Heating Relay#1 : OFF
Heating Relay#2 : OFF
Line 2 If this is a Fan Powered box, this line will display the
Fan On/Off Status. On non-fan powered boxes, this
line will display [Exp Relay 1 Not Used].
Line 3 If your VAV/Zone Controller has been confi gured to
control reheat stages, this line refl ects the On/Off
Status
of
the
fi rst stage of Reheat. If you have 3 stages
of reheat, this line will display the total number of
active
heating
stages.
Examples:
“1 Reheat Stages On” or
“2 Reheat Stages On” or
“3
Reheat
Stages
On”
If proportional heating is used (you have no relays
confi gured for heat), this line will display
“Heating Signal: xxx %”.
Line 4 If your VAV/Zone Controller has been confi gured to
control reheat stages, this line refl ects the On/Off
Status of the second stage of Reheat. If you have 3
stages of reheat as explained on line 2, this line will be
blank.
Status Screen #7 - Alarm Status
XX Box v1.04 IDXXXX
NO ALARMS!
Line 2 Blank
Line 3 NO ALARMS!
This is displayed if no alarms are detected. If there are
one or more alarms active, the possible messages are
shown
below:
SPACE
SENSOR
FAILURE
CFM
SENSOR
FAILURE
DAMPER
OPENING
ALARM
DAMPER
CLOSING
ALARM
HI SPACE TEMP ALARM
LO
SPACE
TEMP
ALARM
DPR
FEEDBACK
FAILURE
For
Alarm
Defi nitions, see the SA Controller
Technical
Guide
or the SA E-BUS Controller
Technical
Guide..
VAV/Zone Controller Status Screens