Programming, Sa controller status screens, Sa controller operator interface 42 – Orion System SA Controller User Manual
Page 42
Zone
Zone
Programming
SA Controller Operator Interface
42
SA Controller Status Screens
Status Screen 9 - Coil Temp & Setpoint
SA Unit v2.20 ID 102
Coil A1 Tmp : XX.XºF
Coil B1 Tmp : XX.XºF
Coil Tmp Spt: XX.XºF
Line 2 Coil A1 Temperature
If a Suction Pressure Transducer has been installed and
confi gured on the unit, the calculated Evaporator Coil
Temperature will appear on this line. If not, this line will
display
0°F.
Line 3 Coil B1 Temperature
If a Suction Pressure Transducer has been installed and
confi gured on the unit, the calculated Evaporator Coil
Temperature will appear on this line. If not, this line will
display
0°F.
Line 4 Coil Temperature Setpoint
During
dehumidifi cation, the Coil Suction Temperature
Setpoint is automatically reset based on the current space
humidity conditions. This is the current calculated Coil
Temperature Setpoint based on that reset.
Status Screen 10 - Coil A2 & B2 Temp
SA Unit v2.20 ID 102
Coil A2 Tmp : XX.XºF
Coil B2 Tmp : XX.XºF
Note:
This screen only applies if you have a WSHP Protection
Module connected to the SA Controller.
Line 2 Coil A2 Temperature
If a Suction Pressure Transducer has been installed and
confi gured on the unit, the calculated Evaporator Coil
Temperature will appear on this line. If not, this line will
display
0°F.
Line 3 Coil B2 Temperature
If a Suction Pressure Transducer has been installed and
confi gured on the unit, the calculated Evaporator Coil
Temperature will appear on this line. If not, this line will
display
0°F.
Status Screen 11 - Static Pressure & Output %
SA Unit v2.20 ID 102
Static Pr...: X.XX”
Press Output: XXX%
[Optional Output]
Line 2 Current Static Pressure
Requires the installation and wiring of a Duct Static
Pressure Sensor. If you do not have a Duct Static Pressure
Sensor correctly installed and wired to the controller, this
line will display “0.0”.
Line 3 Current Static Pressure Output Signal Percentage
Indicates the output signal percentage being supplied to the
VFD Controller or Bypass Damper Actuator when you
have
confi gured one of these options for your HVAC unit.
If you have not confi gured Duct Static Pressure Control,
this line will display [No Press Out Confg].
Line 4 Indicates That This is An Optional Output
This output may or may not have live data to display.
Status Screen 12 - Water Side Economizer
Valve Position & Water Temperature
SA Unit v2.20 ID 102
Water Side Econo
Valve Pos.: XXX %
Water Temp.: XX.XºF
Line 2 Water Side Economizer
This screen pertains to the Water Side Economizer.
Line 3 Valve Position
The Water Side Economizer Valve position will
display on this line.
Line 4 Water Temperature
You must install and confi gure a Entering Water
Temperature Sensor to display the current Water
Temperature.