SA Controller Confi guration Screens

Confi guration Screen #14 - Proof of Flow Input

SA Unit Cnfg ID 102

Proof Of Flow

Input: NO

[0=NO 1=YES]

Enter

<1>

for YES if the unit is equipped with a Proof of Flow Switch

and it is connected to the SA Controller. If selected as YES and the Proof
of Flow Switch is open, only the Supply Fan Relay will be active. If any
other relays such as Heating Stages or Cooling Stages are active, they
will be deactivated when the Proof of Flow Switch input is lost. Enter

<0>

for NO. Default is NO.

Confi guration Screen #15 - Modulating Cooling/

Heating

SA Unit Cnfg ID 102

Mod Cooling: NO
Mod Heating: NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is controlling Modulating Heat-

ing or Modulating Cooling or both. If your HVAC unit is going to use
a Modulating Chilled Water Valve or is equipped with a Digital Com-
pressor, you must select YES for Modulating Cooling. If your HVAC
is using a Modulating Hot Water Valve, Modulating Steam Valve, or a
SCR Controlled Electric Heater, you must select YES for Modulating
Heating. Enter

<0>

for NO. Default is NO.

Confi guration Screen #16 - Modulating

Heating Output Signal

SA Unit Cnfg ID 102

Mod Heating

Output Signal.: 0

[0=0-10V 1=2-10V]

Enter

<0>

for a 0-10 VDC signal to a Modulating Heat Source such

as a Hot Water Valve or SCR Electric Heater. Enter

<1>

for a 2-10

VDC signal to a Hot Water Valve or SCR Electric Heater. Default is
0-10VDC.

Confi guration Screen #17 - Modulating

Heating Reverse Acting

SA Unit Cnfg ID 102

Mod Heating

Rev Acting: NO

[0=NO 1=YES]

Enter

<1>

for YES if the Modulating Heat Source requires 0 VDC to

open and 10 VDC to close. Enter

<0>

for NO. Default is NO.

Confi guration Screen #18 - Modulating

Heating Proportional Window

SA Unit Cnfg ID 102

Mod Heating

Prop. Window.: 10ºF

Time Period..: 5 s

The Modulating Heating Proportional Window is the control range of
the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Heating Proportional Window, the smaller
the signal adjustment per Time Period will be for each ºF the supply air
is from the Active Supply Air Temperature Setpoint. The Time Period is
the delay before another signal increase or decrease can be made and is
user-adjustable. Short Time Periods may cause hunting of the Modulat-
ing Signal. Defaults are 10ºF and 5 seconds.

Confi guration Screen #19 - Chilled Water

Output Signal

SA Unit Cnfg ID 102

Chilled Water

Output Signal: 0

[0= 0-10V 1= 2-10V]

Enter

<1>

for a 2-10 VDC signal or

<0>

for a 0-10 VDC signal to a

Chilled Water Valve for Modulating Cooling Stage 1. If using a Digital
Compressor, select

on the next screen. Default is 0-10V.

Confi guration Screen #20 - Digital Compressor

Signal

SA Unit Cnfg ID 102

Digital Compressor

Signal 1-5V : NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is equipped with a Digital

Compressor for Modulating Cooling Stage 1 or 2. Enter

<0>

for NO.

Default is NO.