Programming, Sa controller scheduling, Sa controller operator interface 36 – Orion System SA Controller User Manual
Page 36: Setting time & date
Zone
Zone
Programming
SA Controller Operator Interface
36
Holiday Start/Stop Times
SA Unit Hldy ID 102
Holiday Schedule
Start Event #1: XXXX
Stop Event #1: XXXX
SA Unit Hldy ID 102
Holiday Schedule
Start Event #2: XXXX
Stop Event #2: XXXX
The fourteen holidays all use the same Start and Stop times which you
program on this screen and the next. You must enter the time in 24-hour
military format, the same as a regular week schedule.
Normally, the holidays will operate in an unoccupied mode or a reduced
schedule mode. There are two start/stop events available on holidays to
match the standard schedule number of events.
Schedule Override
SA Unit Ovrd ID 102
Schedule Override
Enter Override...: X
[0=Auto 1=ON 2=OFF]
If you want to force the unit to operate in a continuous Occupied or
Unoccupied mode, select this menu item to activate the desired method.
If a Schedule Override is active, all other methods of schedule control
are ignored (Push-Button, Internal, and Remote).
As you can see on the last line of the display, enter
<1>
to run continu-
ously in the Occupied Mode or
<2>
to run continuously in the Unoc-
cupied Mode. To restore normal schedule operations, enter
<0>
.
This override remains in effect until canceled and does not time-out like
the Output Overrides do after 10 minutes of no communications.
Note: Do not use the Force OFF mode in place of setting all
the week schedules to ZERO if you are using a Remote
Signal for your scheduling since the Override has priority
over the Remote Signal.
Setting Time & Date
Both the Modular Service Tool and Modular System Manager are
equipped with a real time clock chip allowing them to maintain the
correct time. Once you have programmed the correct time and date, the
information is broadcast globally to all controllers on the entire system.
The System Manager will also broadcast this information once every day
at midnight to synchronize all of the controllers on the system.
Programming Times
From the Main Menu, press
. The following screen will ap-
pear:
1) Set Time & Date
2) Communications
3)
Energy Saving
ESC) Exit Menu
Press
<1>
on your keypad to access the Set Time & Date Screens.
Although the times are displayed on the Main Screen in a standard 12-
hour format, you must program them using the 24-hour military format.
If you confi gured the SA Controller to use its own Internal Schedules,
the Occupied/Unoccupied modes are calculated on the basis of the cur-
rent real time clock reading.
Program Time/Date
Day (Sunday=0): X
Enter Hr. (0-23): XX
Enter Minutes : XX
Day -
Enter the Day of the Week (0 to 6)
Sunday
=
0
Hours (Hr) - Enter Hours in 24-Hour Military Format
(1700
=
5:00
PM)
Minutes -
Enter the Minutes
(0
to
59)
SA Controller Scheduling