SA Controller Operator Interface

Programming

49

VAV/Zone Controller Setpoint Screens

Setpoint Screen #6 - Damper Airfl ow Cool/

Heat Minimum

XX Box Spts IDXXXX

Damper/Airflow Spt

Cool Min.: XXX %
Heat Min.: XXX %

During Supply Air Cooling Mode, if the space being served by this
damper is satisfi ed and has no cooling demand, the damper will close to
this Cool Min setting. This provides a minimum amount of airfl ow into
the space for ventilation, even if the space does not require additional
cooling. During Supply Air Heating Mode, if the space being served
by this damper is satisfi ed and has no heating demand, the damper will
close to this Heat Min setting. This provides a minimum amount of
airfl ow into the space for ventilation, even if the space does not require
additional heating.

Description

Minimum

Default

Maximum

Cool Min

0% or

0 CFM

10% or

1000 CFM

100% or

30000 CFM

Heat Min

0% or

0 CFM

10% or

100 CFM

100% or

30000 CFM

Setpoint Screen #7 - Damper Airfl ow Night Min

and Fan On Min

XX Box Spts IDXXXX

Damper/Airflow Spt

Night Min.: XXX %
Fan On Min.:

XXX %

The Night Min is the position the damper will move to when the sys-
tem is in Override Mode and this particular damper is not part of the
override group. This Night Min position only affects non-fan powered
boxes. The Fan On Min is the minimum damper or airfl ow setting used
to activate the parallel fan if installed. Pressure Independent = CFM.
Pressure Dependent = %.

Description

Minimum

Default

Maximum

Night Min

0% or

0 CFM

0% or

0 CFM

100% or

9999 CFM

Fan On Min

0% or

0 CFM

25% or

250 CFM

100% or

9999 CFM

Setpoint Screen #8 - Damper Airfl ow Reheat Min

XX Box Spts IDXXXX

Damper/Airflow Spt

Reheat Min.: XXX %

The Reheat Min is the damper or airfl ow setting used during the Space
Reheat Mode of operation.

Description

Minimum

Default

Maximum

Reheat Min

0% or

0 CFM

0% or

0 CFM

100% or

30000 CFM

Setpoint Screen #9 - Damper Airfl ow Fixed

Position

XX Box Spts IDXXXX

Damper/Airflow Spt

Fixed Pos: XXX %

Many times while troubleshooting a system, it is useful to have the zone
damper set to a specifi c damper position or airfl ow setting. This setpoint
can be used to determine where the damper/airfl ow will remain when the
VAV/Zone Controller receives a Force to Fixed Position command.

Description

Minimum

Default

Maximum

Fixed Pos

0% or

0 CFM

0% or

0 CFM

100% or

9999 CFM

Setpoint Screen #10 - SAT HVAC Mode

Deadband

XX Box Spts IDXXXX

SAT HVAC Mode

Deadband.: XXºF

If the supply air temperature is above the space temperature by this
amount, the VAV/Zone controller enters the Supply Air Heating Mode. It
will remain in the Supply Air Heating Mode until the supply air drops to
2ºF above the space temperature. At that point the unit enters the Supply
Air Vent Mode and remains there until the supply air drops this deadband
below the space temperature. At that point the VAV/Zone Controller en-
ters the Supply Air Cooling Mode and will remain there until the supply
air temperature rises to 2ºF below the space temperature.

Description

Minimum

Default

Maximum

SAT HVAC Mode

Deadband

0ºF

10ºF

20ºF