(4) Checking gas leak

1) Remove the charging hose (green) from the

vacuum pump, and connect the hose to the
refrigerant cylinder (R-410A).

2) Loosen the nut on the gauge manifold side of the

charging hose (green).

3) Open the valve of refrigerant cylinder and

perform air purging in the charging hose (green).
Then tighten the nut.

4) Open the high pressure valve of the gauge

manifold. Charge the system with refrigerant until
the low pressure gauge indicates 57 psi
(0.39 kPa). After charging is complete, close the
high pressure valve.

5) Open the valve of refrigerant cylinder and

perform air purging in the charging hose (green).
Then tighten the nut.

6) Check carefully for gas leaks inside the

refrigeration system using the gas leak tester.

7) Repair any leak.

WARNING

Any repair on a charged system should be
performed by a licensed professional only.

WARNING

Before checking for gas leaks, fully confirm
that there is nothing flammable in the area
to cause an explosion or fire. Contact of
refrigerant with an open fire generates
toxic gas.

I001901

Open The Valve
of Refrigerant
Cylinder

To Process Tube Fitting

Charging Hose
(Green)

Refrigerant

Cylinder R-410A

Red

LO

Closed

HI

Closed

Valve Setting

Air Purging

I002228

LO

Closed

HI

Open

LO

Closed

HI

Closed

Refrigerant

Cylinder R-410A

Valve Setting

Gauge Reading

57 psi

(390 kPa)

Open High Pressure
Valve

High Pressure
Side Tube

Low Pressure
Valve (Closed)

Process Tube Fitting

Refrigerant
Cylinder
Valve
(Open)