5.7 Drain Switch

• The Climate Pro 18 is equipped with a drain switch. When the drain tank accumulates

approximately 4.0 gal (15 L) of condensate (water) in the drain tank, the drain switch sends a
signal to the microprocessor. The microprocessor stops all operation of the unit, displays the
"FL" on the LCD and closes the contact of output signal.

• This system utilizes a 0.1 A, 125/250 VAC micro-switch for this function. When drain water

accumulates approximately 4.0 gal (15 L) in the drain tank, the drain tank base plate, which is
supported at its fulcrum, is pushed down in the arrow direction as shown in the figure below.

• When the drain tank base plate is forced down, the top of the drain tank base plate turns off the

contacts #1-#2 of the micro switch. This causes the ground signal at the CN18 connector of the
relay board to go open. When the microprocessor detects this event, it shuts the unit off, displays
the "FL" on the LCD and closes the contact of output signal.

• When the drain tank is removed (or the drain tank is emptied), the top of the drain tank base

plate returns to its original position from the tension of the coil spring. Then contacts #1-#2 of
the drain switch close. This provides a ground to the microprocessor through the CN18
connector.

ILL00873-00

2

NC

C

1

DS2

DS1

Indoor Heat Exchanger

Drain Pan

Drain Tube

Drain Tank

Fulcrum

Drain Water

Base Plate Top

Base Plate

Base Plate Bottom

Drain Switch

Spring

To CN18