Repair Section

66

Troubleshooting of Unit does not operate - Table 5

Condition

Check Area/Diagnostic

Code

Possible Cause

Remedy

Unit does
not operate.

LCD
displays
self-
diagnostic
codes.

E4

Loose CTS2 thermistor
connection

Reconnect the CTS2
thermistor and check
connection.

Defective CTS2 thermistor
(short or open)

Replace the CTS2
thermistor.

E5

Loose CTS3 thermistor
connection

Reconnect the CTS3
thermistor and check
connection.

Defective CTS3 thermistor
(short or open)

Replace the CTS3
thermistor.

LCD
displays
notification.

OUTSIDE OPERATING
RANGE

Unit is operating outside
operating range.

Check product specification
for temperature operating
range.
Press any key to exit.

DEFROST

Unit is under defrost control. Wait until defrost control is

completed.

KEY LOCKED

Buttons on the control panel
are locked.

Press and hold MENU/ESC
button for 5 seconds to
unlock.

EXTERNAL THERMOSTAT
ACTIVATED

Status is changed to control
by an external thermostat.

Operate the unit by an
external thermostat.

LCD shows
normal, but
the unit does
not start.

Set point temperature

Room temperature
reached the set point
temperature and the unit
operation stopped.

Adjust the set point
temperature.

Unit stops
immediately
after
starting.

LCD
displays
normally.

Fan on-off relay on the relay
board

Open circuit or insufficient
contact surface area

Replace the relay board.

Fan speed change relay on
the relay board

Open circuit or insufficient
contact surface area

Replace the relay board.

Fan motor insulation
resistance

Insulation failure on the fan
motor

Replace the fan motor.

Compressor relay on the
relay board

Open circuit or insufficient
contact surface area

Replace the relay board.

Compressor insulation
resistance

Insulation failure on
the compressor

Replace the compressor.