beautypg.com

2 removal of refrigeration cycle components, Removal of refrigeration cycle components – MovinCool Climate Pro 18 Service Manual User Manual

Page 88

background image

Repair Section

88

10.2 Removal of Refrigeration Cycle Components

WARNING

• Before replacing any refrigeration cycle component, recover the refrigerant using

standard recovery procedures and equipment.

• When recovering the refrigerant, use the pinch-off tubes at the low pressure side (tube 1)

and high pressure side (tube 2) as shown in the figure below.

CAUTION

• To prevent oxidation, dry nitrogen should be conducted (flow rate 0.27 gal/min (1 L/min)) through

the pinch-off tube during any brazing operation.

• During any component replacement involving brazing, shield nearby parts with a steel plate, etc.,

to protect them from the flame.

< NOTE >

When replacing the compressor, attach the pipe 1 and the pipe 2 packaged in the compressor
assembly.

ILL00910-00

Compressor

A, B

A, B, C, D

C, F, G, H

N, O

C, D

E

Indoor Heat Exchanger

Outdoor Heat Exchanger

High Pressure Switch

Electronic Expansion Valve

Distributor

Part to Replace

Disconnect At

C

Pipe 1

Pipe 2

E

B

Tube 2

N

Tube 1

O

A

D

F

G