Repair Section

60

Troubleshooting of Insufficient Cooling or Heating - Table 1

Condition

Check Area

Possible Cause

Remedy

Insufficient Cooling

or Heating

Air volume
normal

Compressor
operates.

Usage conditions
(high/low temperature)

Operates near minimum or
maximum of operation
range.

Review the installation
place.

Dirt in the indoor or outdoor
heat exchanger

Insufficient heat exchange

Clean the heat
exchangers.

Frost in the refrigeration
system

Clogging at the frost section

Service the refrigeration
system.

No temperature difference
between indoor and outdoor
heat exchangers

Insufficient refrigerant

Check the leaking part,
then repair and charge
the correct amount of
refrigerant.

Compressor
does not
operate.

Voltage

Low voltage

Repair the power supply.

Compressor relay on the
relay board

Open circuit or insufficient
contact surface area

Replace the relay board.

Capacitor for compressor
motor

Capacitor malfunction

Replace the capacitor.

Compressor coil resistance
(0 ohm or

∞ ohm)

Short or open circuit

Replace the compressor.
(In case of short, check
the compressor relay.)

Abnormal
air volume

No air

Fan on-off relay on the relay
board

Open circuit or insufficient
contact surface area

Replace the relay board.

Coil resistance of indoor or
outdoor fan motor
(0 ohm or

∞ ohm)

Short or open circuit

Replace the fan motor.

Insufficient
air volume

Air filter

Clogged air filter

Clean the air filter.

Indoor or outdoor heat
exchanger

Clogged indoor or outdoor
heat exchanger

Clean the indoor or
outdoor heat exchanger.

Crushed fins

Repair or replace the
heat exchanger.

Duct connection state

Improper connection

Repair duct connection.

Indoor or outdoor fan motor

Abnormal rotation

Replace the fan motor.

Fan speed change relay on the
relay board

Open circuit or insufficient
contact surface area

Replace the relay board.