3. SPECIFICATIONS

3.1 Technical Specifications

Technical Specifications - Table 1

< NOTE >

*1 : With outdoor heat exchanger air outlet duct 10 feet (3.0 m) vertical head lift from the ground to the ceiling.

ITEM

SPECIFICATIONS

Electronic Features

Operation

Digital Programmable

Electrical Characteristics

Voltage Requirement

1 Phase, 115 V, 60 Hz

Operating Voltage Range Max.

127 V

Min.

104 V

Starting Current

65 A

Recommended Fuse Size

20 A

FLA

15.6 A

LRA

65 A

Cooling Performance

Rating Condition
(AHAM PAC-1-2009)

Indoor Heat Exchanger:
80 °F

(26.7 °C), 50 %RH

Outdoor Heat Exchanger:
80 °F (26.7 °C), 50 %RH

Total Cooling Capacity*

1

14,600 Btu/h (4,270 W)

Sensible Cooling Capacity*

1

9,900 Btu/h (2,900 W)

Power Consumption*

1

1.54 kW

Current Consumption*

1

14.1 A

SD-EER

9.5

Power Factor

95 %

Heating Performance

Rating Condition
(AHAM RAC-1-2008)

Indoor Heat Exchanger:
70 °F (21.1 °C), 57 %RH
Outdoor Heat Exchanger:
47 °F (8.3 °C), 75 %RH

Total Heating Capacity

13,700 Btu/h (4,010 W)

Power Consumption

1.61 kW

Current Consumption

14.7 A

COP

2.49

Power Factor

95 %

Compressor

Type

Hermetic Rotary

Output

1.16 kW

Ventilation Equipment for
Outdoor Coil

Type of Outdoor Coil (Heat Exchanger)

Plate Fin

Type of Fan

Centrifugal Fan

Air Flow

700 CFM (1,190 m

3

/h)

Max. External Static Pressure

0.23 IWG (57 Pa)

Motor Output

0.135 kW