Specifications, 1 technical specifications, Technical specifications – MovinCool Climate Pro 18 Service Manual User Manual
Page 12

Operation Section
12
3. SPECIFICATIONS
3.1 Technical Specifications
Technical Specifications - Table 1
< NOTE >
*1 : With outdoor heat exchanger air outlet duct 10 feet (3.0 m) vertical head lift from the ground to the ceiling.
ITEM
SPECIFICATIONS
Electronic Features
Operation
Digital Programmable
Electrical Characteristics
Voltage Requirement
1 Phase, 115 V, 60 Hz
Operating Voltage Range Max.
127 V
Min.
104 V
Starting Current
65 A
Recommended Fuse Size
20 A
FLA
15.6 A
LRA
65 A
Cooling Performance
Rating Condition
(AHAM PAC-1-2009)
Indoor Heat Exchanger:
80 °F
(26.7 °C), 50 %RH
Outdoor Heat Exchanger:
80 °F (26.7 °C), 50 %RH
Total Cooling Capacity*
1
14,600 Btu/h (4,270 W)
Sensible Cooling Capacity*
1
9,900 Btu/h (2,900 W)
Power Consumption*
1
1.54 kW
Current Consumption*
1
14.1 A
SD-EER
9.5
Power Factor
95 %
Heating Performance
Rating Condition
(AHAM RAC-1-2008)
Indoor Heat Exchanger:
70 °F (21.1 °C), 57 %RH
Outdoor Heat Exchanger:
47 °F (8.3 °C), 75 %RH
Total Heating Capacity
13,700 Btu/h (4,010 W)
Power Consumption
1.61 kW
Current Consumption
14.7 A
COP
2.49
Power Factor
95 %
Compressor
Type
Hermetic Rotary
Output
1.16 kW
Ventilation Equipment for
Outdoor Coil
Type of Outdoor Coil (Heat Exchanger)
Plate Fin
Type of Fan
Centrifugal Fan
Air Flow
700 CFM (1,190 m
3
/h)
Max. External Static Pressure
0.23 IWG (57 Pa)
Motor Output
0.135 kW