Operation Section

45

6.2 24VAC Thermostat Connection (Field Supplied)

• An optional 24VAC transformer is required with a field supplied 24VAC thermostat.

WARNING

Disconnect power before installation. Beware that some residual voltage may remain in
the unit immediately after the power is disconnected.

1) Turn the unit off and unplug the power cord. Refer to the previous section to remove the service

panel and insert the thermostat wires through the hole in the rear panel. Connect the 24VAC
thermostat wires to the terminal block according to the 24VAC thermostat connection table
shown above.

2) Install the 24VAC secondary class 2 transformer to the service box. Insert the secondary side

wires through the upper grommet hole in the service box. Connect the wires to the terminal
blocks according to the 24VAC transformer connection table shown above. All wiring must
comply with applicable local codes, ordinances, and regulations.

Specifications:

- Transformer: Primary 115 V, Secondary 24 V
- Recommended wire size: 18 AWG or 20 AWG

24VAC Thermostat Connection Table

24VAC Transformer Connection Table

24VAC RC/RH

24VAC C

24VAC

Thermostat

Wire No.

Unit

Terminal Block 3

Terminal No.

O/B

G

Y

C

O/B

RC/RH

G

Y

R1

24VAC

Trasformer Wire

No.(Primary Side)

Unit

Terminal Block 1

Terminal No.

T1

R1

T1

24VAC Hot

24VAC

Trasformer Wire

No.(Secondary Side)

Unit

Terminal Block 3

Terminal No.

24VAC Neutral

Hot

Neutral

Jumper Plug

24VAC Thermostat

24VAC Transformer

Primary

Secondary

TB3

TB1

Service Box

N
eutralNeutral HotHot

ILL00880-00