9.10 Inspection of Electronic Expansion Valve Control Coil

• Check resistance across the connector pins of

the electronic expansion valve control coil. Coil
resistance should be between 26 to 56 ohm at
room temperature.

- Between Blue and Red
- Between Orange and Red
- Between Yellow and Red
- Between White and Red

• If the resistance reading does not meet the

above condition, replace the electronic
expansion valve control coil.

9.11 Inspection of 4-Way Valve Controller Coil

• Check resistance across the connector pins of

the 4-way valve controller coil. Coil resistance
should be between 350 to 520 ohm at room
temperature.

• If the resistance reading does not meet the

above condition, replace the 4-way valve
controller coil.

9.12 Inspection of Thermistor

• Using an ohmmeter, check the resistance

value across the 2-pin connector.

• Thermistors:

- Indoor air inlet thermistor (RTS)
- Outdoor air inlet thermistor (ODS)
- Indoor pipe thermistor (CTS1)
- Compressor pipe thermistor (CTS2)
- Outdoor pipe thermistor (CTS3)

ILL00906-00

7 6 5 4 3 2 1

Connector Number

Wire Color

1

Red

2

Blue

3

Orange

4

Yellow

5

6

7

White

Not in use

Not in use

ILL00862-00

I003204

0

5

10

15

20

32

(0)

41

(5)

50

(10)

59

(15)

68

(20)

77

(25)

86

(30)

95

(35)

104

(40)

133

(45)

122

(50)

Temp.

°

F (

°

C)

Resistance (k ohm)

Thermistor Specification