Troubleshooting of Insufficient Cooling or Heating - Table 2

< NOTE >

Under heating mode operation, when the room temperature is higher than 68 °F (20 °C), the low
fan speed option is deactivated and switched to medium fan speed to prevent high pressure
protection activation.

Condition

Check Area

Possible Cause

Remedy

Insufficient Cooling

or Heating

No hot air
during
HEAT
mode
operation

LCD display
shows
HEAT
mode, but
operates in
COOL
mode.

F1 fuse (1.5 A)

F1 fuse (1.5 A) is blown.

Replace the F1 fuse
(1.5 A).

4-way valve

4-way valve failure

Replace the coil on the 4-
way valve.