3) overflow of drain water – MovinCool Climate Pro 18 Service Manual User Manual
Page 67

Repair Section
67
Troubleshooting of Unit does not operate - Table 6
(3) Overflow of drain water
Condition
Check Area
Possible Cause
Remedy
Unit stops
after
running for
a while.
LCD
displays
normally.
Temperature of fan motor
(abnormally high)
Activation of the internal
overload relay (IOLF) due to
fan motor malfunction
Replace the fan motor.
Temperature of
compressor (abnormally
high)
Activation of the overload
relay (IOLC) due to the
defective overload relay
Inspect the overload relay. If
defective, replace it.
Activation of the overload
relay (IOLC) due to the
defective compressor
Inspect the compressor. If
defective, replace it.
Refrigerant leakage
Insufficient refrigerant or gas
leakage
Repair and charge
refrigerant.
Dirt on indoor or outdoor
heat exchanger
Insufficient cooling or
heating of the heat
exchanger
Clean the heat exchanger.
Duct connection state
Improper connection
Repair duct connection.
Condition
Check Area
Possible Cause
Remedy
Overflow of water from the
unit
Indoor or outdoor drain pan
Cracks in the drain pan
Check and replace the
drain pan.
Drain hole of the indoor or
outdoor drain pan
Clogged drain hose
Check and repair the
drain hose.
Clogged air filter
Reversed air flow from the
drain hole due to excessive
negative pressure inside of
the unit
Clean the air filter.