MovinCool Climate Pro 18 Service Manual User Manual

Page 92

background image

Repair Section

92

(3) Checking vacuum

1) Leave the high pressure valve and the low

pressure valve of the gauge manifold closed for 5
minutes or more, and confirm that the gauge
pointer does not return to zero.

2) If the gauge pointer returns gradually to zero

there is a leak somewhere in the system (this
could also include gauge manifold). Perform leak
check according to procedure indicated in the
next step. Once leak has been found and
repaired, evacuate the system once more and
confirm the system holds vacuum.

ILL00085-00

Return

Pipe Brazing

LO

Closed

HI

Closed

Valve Setting

Pressure Gauge