42 ~aa5ppss – Measurement Computing CB-COM-7012 User Manual
Page 65
65
CB-7012, CB-7014, CB-7017 User’s Manual
2.42 ~AA5PPSS
Description: Set PowerOn Value and Safe Value
Note: This command is for CB-7012/12D/12F/12FD/14D only.
Syntax: ~AA5PPSS[CHK](cr)
~
Delimiter character
AA
Address of module to set (00 to FF)
5
Command for setting PowerOn Value and Safe Value
PP
PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on,
DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
SS
Safe Value, 00=DO0 off, DO1 off, 01=DO0 on, DO1
off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
Response: Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of responding module (00 to FF)
Example:
Command: ~0150003
Receive: !01
Set Address 01 PowerOn Value is DO0 off, DO1 off, Safe
Value is DO0 on, DO1 on, return successful.
Related Command:
Sec.2.41, ~AA4
Related Topic:
Set. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation