beautypg.com

42 ~aa5ppss – Measurement Computing CB-COM-7012 User Manual

Page 65

background image

65

CB-7012, CB-7014, CB-7017 User’s Manual

2.42 ~AA5PPSS

Description: Set PowerOn Value and Safe Value

Note: This command is for CB-7012/12D/12F/12FD/14D only.

Syntax: ~AA5PPSS[CHK](cr)

~

Delimiter character

AA

Address of module to set (00 to FF)

5

Command for setting PowerOn Value and Safe Value

PP

PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on,

DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

SS

Safe Value, 00=DO0 off, DO1 off, 01=DO0 on, DO1

off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

Response: Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of responding module (00 to FF)

Example:

Command: ~0150003

Receive: !01

Set Address 01 PowerOn Value is DO0 off, DO1 off, Safe

Value is DO0 on, DO1 on, return successful.

Related Command:

Sec.2.41, ~AA4

Related Topic:

Set. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation