33 $aa7(tl)(th) – Measurement Computing CB-COM-7012 User Manual
Page 56
56
CB-7012, CB-7014, CB-7017 User’s Manual
2.33 $AA7(TL)(TH)
Description: Set Target Low/High Values for Linear Mapping
Note: The command is for CB-7014D only.
This command must follow the $AA6(SL)(SH) command.
Syntax: $AA7(TL)(TH)[CHK](cr)
$
Delimiter character
AA
Address of module to set (00 to FF)
7
Command for setting target values
TL
target low level value in engineering unit format
TH
target high level value in engineering unit format
Response: Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of responding module (00 to FF)
Example:
Command: $076
−
10.000+10.000 Receive: !01
Set Address 01 target value
−
10 to +10, return successful.
Related Command:
Sec. 2.30, $AA3; Sec. 2.31, $AA5; Sec. 2.32, $AA6(SL)(SH)
Related Topic:
Sec. 3.8, Linear Mapping