beautypg.com

29 @aace – Measurement Computing CB-COM-7012 User Manual

Page 52

background image

52

CB-7012, CB-7014, CB-7017 User’s Manual

2.29 @AACE

Description: Clear Event Counter

Note: This command is for CB-7012/12D/12F/12FD/14D only.

Syntax: @AACE[CHK](cr)

@

Delimiter character

AA

Address of module (00 to FF)

CE

Command to clear event counter

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of responding module (00 to FF)

Example:

Command: @01RE

Receive: !0101234

Read Address 01 event counter;

returns 1234.

Command: @01CE

Receive: !01

Clear Address 01 event counter, return successful.

Command: @01RE

Receive: !0100000

Read Address 01 event counter, return 0.

Related Command:

Sec. 2.28 @AARE

Related Topic:

Sec. 3.4 Digital Input and Event Counter

This manual is related to the following products: