CB-7012, CB-7014, CB-7017 User’s Manual

2.30 $AA3

Description: Read Source Low/High Values for Linear Mapping

Note: This command is for CB-7014D only.

Syntax: $AA3[CHK](cr)

$

Delimiter character

AA

Address of module (00 to FF)

3

Command for reading source values

Response: Valid Command:

!AA(SL)(SH)[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of responding module (00 to FF)

SL

Low limit of source values in engineering unit format.

SH

High limit of source values in engineering unit format.

Example:

Command: $013

Receive: !01-10.000+10.000

Read Address 01 source value, return from -10 to +10.

Related Command:

Sec. 2.31, $AA5; Sec. 2.32, $AA6(SL)(SH); Sec. 2.33,

$AA7(TL)(TH)

Related Topic:

Sec. 3.8, Linear Mapping