CB-7012, CB-7014, CB-7017 User’s Manual

2.23 @AALO(Data)

Description: Set Low Alarm

Note: This command is for CB-7012/12D/12F/12FD/14D only.

Syntax: @AALO(Data)[CHK](cr)

@

Delimiter character

AA

Address of module to set (00 to FF)

LO

Command for setting low alarm value

(Data)

low alarm values, data format is in engineering units.

Response: Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of responding module (00 to FF)

Example:

Command: @01LO-10.000

Receive: !01

Set Address 01 low alarm -10.000; return successful.

Related Command:

Sec. 2.21, @AAEAT; Sec. 2.27, @AARL

Related Topic:

Sec. 3.6, High/Low Alarm