beautypg.com

20 @aado(data) – Measurement Computing CB-COM-7012 User Manual

Page 43

background image

43

CB-7012, CB-7014, CB-7017 User’s Manual

2.20 @AADO(Data)

Description: Set Digital Output

Note: This command is for CB-7012/12D/12F/12FD/14D only.

Syntax: @AADO(Data)[CHK](cr)

@

Delimiter character

AA

Address of module to set (00 to FF)

DO

Command for set digital output

(Data)

output value, 00=DO0 off, DO1 off, 01=DO0 on, DO1

off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid command

?

Delimiter for invalid command. When the alarm is

enabled, the command will return invalid.

AA

Address of responding module (00 to FF)

Example:

Command: @01DO00

Receive: !01

Set Address 01 digital output 00, return successful.

Related Command:

Sec. 2.19, @AADI; Sec. 2.21, @AAEAT; Sec. 2.24, @AADA

Related Topic:

Sec. 3.5, Digital Output