32 $aa6(sl)(sh) – Measurement Computing CB-COM-7012 User Manual
Page 55

55
CB-7012, CB-7014, CB-7017 User’s Manual
2.32 $AA6(SL)(SH)
Description: Set Source Low/High Values for Linear Mapping.
Note: This command is for CB-7014D only.
The data are stored in EEPROM.
Syntax: $AA6(SL)(SH)[CHK](cr)
$
Delimiter character
AA
Address of module to set (00 to FF)
6
Command for setting source values
SL
Source low level value
SH
Source high level value
Response: Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of responding module (00 to FF)
Example:
Command: $016
−
10.000+10.000 Receive: !01
Set Address 01 source value
−
10 to +10; return successful.
Related Command:
Sec. 2.30, $AA3; Sec. 2.31, $AA5; Sec. 2.33, $AA7(TL)(TH)
Related Topic:
Sec. 3.8, Linear Mapping